4 Zone Conventional Fire Alarm Control Panel


Specification

  • 4 zones.Each zone can have maximum 32 conventional
    detectors. The total number of detectors and call points in a zone
    shall not exceed 32
  • Each zone can be programed work as fire alarm (default) or
    supervisory alarm mode
  • Each zone include 2 indicators, 1st indicator is bi-color( Red and
    Green), factory default to indicate fire condition. Red color on in case
    fire signal triggered; also can be programed to indicate supervisory
    condition. Green color on in case superisory signal triggered. 2nd
    abmer indicator flashes when the zone is in fault condition(0.5:0.5).
    And it illuminates steadily when the zone is disabled or in test mode
  • 1x Alarm output can be setup as 24V or N/O,N/C
  • 3x sounder outputs, output 1 can be setup 24V or N/O N/C,output 2 and 3 only work as 24V output
  • 1x Disable/supervisory relay ouput (N/O COM N/C)
  • 1 x Fault output (N/O COM N/C)
  • 1x Auxilary power output: output current 450mA in standby mode and Maximum 1000mA in alarm mode when the Alarm Output been set to a normally open/close contact type
  • Able to report short circuit and open circuit of detection zones, sounder outputs and alarm output
  • Designed with standby batteries and space provision for two sealed lead-acid batteries
  • Easy operation to enable/disable zones, sounder outputs and alarm output
  • Alarm Test function selectable with or without sounder notification
  • Output programmable for interlink between zones and sounder outputs, alert or evacuate tone, with or without delay
  • Different Silence/Reset/Test modes can be selected to meet local requirement
  • Remote controls available for silence evac and reset
  • Three access levels settable via key control
  • Reserved repeater panel interface for fire alarm indication of multiple zones