4 zones.Each zone can have maximum 32 conventional
detectors. The total number of detectors and call points in a zone
shall not exceed 32
Each zone can be programed work as fire alarm (default) or
supervisory alarm mode
Each zone include 2 indicators, 1st indicator is bi-color( Red and
Green), factory default to indicate fire condition. Red color on in case
fire signal triggered; also can be programed to indicate supervisory
condition. Green color on in case superisory signal triggered. 2nd
abmer indicator flashes when the zone is in fault condition(0.5:0.5).
And it illuminates steadily when the zone is disabled or in test mode
1x Alarm output can be setup as 24V or N/O,N/C
3x sounder outputs, output 1 can be setup 24V or N/O N/C,output 2 and 3 only work as 24V output
1x Disable/supervisory relay ouput (N/O COM N/C)
1 x Fault output (N/O COM N/C)
1x Auxilary power output: output current 450mA in standby mode and Maximum 1000mA in alarm mode when the Alarm Output been set to a normally open/close contact type
Able to report short circuit and open circuit of detection zones, sounder outputs and alarm output
Designed with standby batteries and space provision for two sealed lead-acid batteries
Easy operation to enable/disable zones, sounder outputs and alarm output
Alarm Test function selectable with or without sounder notification
Output programmable for interlink between zones and sounder outputs, alert or evacuate tone, with or without delay
Different Silence/Reset/Test modes can be selected to meet local requirement
Remote controls available for silence evac and reset
Three access levels settable via key control
Reserved repeater panel interface for fire alarm indication of multiple zones