Specification
Detection system | Ultraviolet rays detection (Detected wave length <185 to 260nm>) |
Coverage | 33ft. (10m) Gas Flame of Lighter in front of sensor : approx. 2.75”(7cm)33ft.(10m)[2.75″(7cm)flame]100ft. (30m) Flame of N-heptane on fire plate 15cm×15cm: approx. 23.62”(60cm) *The flame size is rough.• Angle Vertical: approx. 75degrees (upward: 15degrees) Hrizontal: approx. 100degrees (downward: 60degrees) |
Supply voltage | 10V to 30VDC (non-polarity) |
Current consumption | 35mA or less |
Alarm output | • Dry contact relay Form C (alarm : open/close) Contact capacity: 30V(AC/DC)0.5A or less(resistance load)• Operation time: The following are selectable Detection time + off delay operation approx. 2sec. – 1 min. Detection time + off delay operation approx. 5sec. – 10 min.• Output operation: The following are selectable Same time as above continuous outoput Same time as above flashing output• Operation mode (day/night time discernment function): 5lux (night time operation) – ∞lux (day time operation) adjustment volume |
Alarm memory | LED (yellow) blinking and lights on /or LED disable. [selectable by switch] |
LED indicator | Operation LED (red): synchronous dry contact relay Memory indication LED (yellow): After blinking for 3 minutes and auto reset after 47 minutes or manually reset |
Adjustment | Adjustment range Vertical: downward 90degrees (horizontal – vertical) Horizontal: 180degrees |
Sensitivity adjustment | ・ Sensitivity H(100%), L(50%)[selectable by switch]・ Detection timer 1sec., 6sec., 15sec., 30sec., [selectable by switch] |
Mounting position | Indoor, Outdoor |
Wiring | Power supply: 2 Dry contact: 3 |
Weight | Approx. 19.3oz (550g) |
Appearance | Sensor part: PC resin (white) Adjustment, mounting part: AES resin (white) |
Accessory | Tapping screw Φ6 × 30(SUS): 4pcs Tapping screw Φ4 × 8(SUS): 1pc Band: 1pc Area mask seal: 1pc |
ENVIRONMENTAL SPECIFICATION | |
---|---|
Ambient temperature | -4°F to + 122°F (-20°C to +50°C) |